NOTES ON INSTALLATION
Claro Smart Switch for Caseta DVRF-5NS
Documentation
- Specification Sheet
- Installation Guides
KNOWLEDGE ARTICLE CONTENTS:
Section (1): Switch Load RatingsSection (2): Product Installation
Section (3): Product Settings
Section (4): Troubleshooting
Section (1): Switch Load Ratings
MODEL | VOLTAGE | NEUTRAL CONNECTION REQUIRED | WIRE TO 3-WAY SWITCH | LOAD TYPE | MINIMUM LOAD | MAXIMUM LOAD |
DVRF-5NS | 120V | YES | YES | INC/HALOGEN LED FAN MOTOR ELV MLV | 10 WATT 0.1 A 0.1 A 10 WATT 10 WATT | 600 WATT 5 AMP 3.0 AMP 600 WATT 600 VA |
Section (2): Product Installation
NOTES ON INSTALLATION
- Neutral wire required.
- Can wire to mechanical 3-way switch in 3 way applications.
- Use with Pico remote for 3-way and multi-location dimming (Pico sold separately)
- Up to 10 Pico remotes can be paired with 1 Diva Smart Dimmer
- If there is no ground wire in your electrical box, cap off the green wire from the switch. A ground wire connection is not required for this switch to function properly. A ground wire may be required by local electrical code.
The ADVANCED INSTALLATION GUIDE will guide you through several additional installation topics beyond what was covered in this article.
Section (3): Product Settings
Status LED Indicator Light
Has a white soft glow status LED to indicate load status.
Note:
This can only be disabled/enabled with the use of the Lutron App. Please see the steps to do so below.
Step 1
Tap on the Claro Smart Switch from the Devices area in the Lutron App. Then select "Edit Device".
Step 2
Tap on the "Status LED".
Step 3
Select "On" or "Off" (default is On) and then tap on "Save" in the top right corner of the screen.
Section (4): Troubleshooting
Section (3): Product Settings
Status LED Indicator Light
Has a white soft glow status LED to indicate load status.
Note:
This can only be disabled/enabled with the use of the Lutron App. Please see the steps to do so below.
Step 1
Tap on the Claro Smart Switch from the Devices area in the Lutron App. Then select "Edit Device".
Step 2
Tap on the "Status LED".
Step 3
Select "On" or "Off" (default is On) and then tap on "Save" in the top right corner of the screen.
Section (4): Troubleshooting
Symptoms | Probable cause and action |
Light does not turn on or switch LED does not light up. | • Red and black wires on the switch are reversed. • Light bulb(s) burned out. • Breaker is OFF or tripped. • Light not properly installed. • Wiring error. • FASS on the switch is in the Off position |
Light does not respond to Pico remote control. | • The switch failed to pair with Pico remote control; see Pairing the switch and Pico remote control. • The switch is already at the light level the Pico remote control is sending. • The Pico remote control is outside the 30 ft (9 m) operating range. • The Pico remote control battery is low. • The Pico remote control battery is installed incorrectly |
Load is Off and the status LED is blinking 4 times, pause, and repeats. | • The switch is in an Over Temperature Protection (OTP) mode. • Ensure Ganging and Derating has been accounted for so that the switch is not overloaded. • Reset the switch by using the FASS, (Front Accessible Service Switch) located under the Off button. Pull out the FASS and push it back in. |